Cordex CXC brings advanced technology to the DC power industry. This compact system controller is designed for seamless operation and set up of Argus power systems and is equipped with a complete range of features.

A graphic LCD display with a state-of-the-art touch-screen interface allows simple and convenient local set up, control, and monitoring of Cordex rectifiers. By utilizing TCP/IP technology, complete configuration and monitoring of power equipment is possible through a network web browser.

The Cordex CXC system controller ensures effortless operation of the Cordex rectifier family. Time consuming, complicated set up and monitoring of DC power systems or smart peripheral modules is now a thing of the past.

  • LCD touch-screen user interface
  • Internet ready, integrated SNMP
  • High reliability CAN bus communication
  • User definable alarms
  • Flexible battery management features
  • Smart peripheral features

Technische Daten   

Features

User Interface
GUI:

 
Use internet browser (IE6 and above) to
access embedded GUI through Ethernet
port or RS-232 craft port
Display: Full graphic LCD, 160x160 pixels, with backlight
and contrast adjustment
Audio: Built in speaker for alarms and popup messages
Indicators:

 
System OK — Green
Minor alarm — Yellow
Major alarm — Red
Controls: LCD touch screen with virtual alpha numeric
and numeric keyboards
Language: Multi language support including Chinese characters

Alarm:
Relays: Potential free Form C contacts
SNMP: Compatible with HP Openview, SNMPc
Email: Via modem

Communication Ports
RS-232 port: Craft port on front panel for local connection and optional 2nd port on rear panel for
remote connection via external modem series
CAN: Interface to Cordex series rectifiers and optional smart peripheral modules
Ethernet: 10/100 Base T With half/full duplex
Modem: Optional internal or external modems with dial back security and password control

Data Logging
Daily Statistics:
 
Minimum, maximum and average on analog input channels, with date and time stamp
Battery current, rectifier current, and AC mains voltage for last 90 days
Event Log: All events such as alarms, power on, change of state on digital inputs or other events
Battery Log: Battery health history on last 20 discharges with time of discharge and battery capacity

Control Functions:

Battery temperature compensation
Automatic, scheduled (periodic) or manual equalize
Automatically terminated equalize charge
Battery current terminate equalize
Dynamic charge current control
Multiple LVD controls
Battery capacity and runtime prediction
Battery mid-point monitoring
Auto or manual battery test

Smart Peripheral Modules
Shunt multiplexer: Monitors up to 16 shunts per module
Battery cell monitor: 1 string of 2V cells or 4 strings of 12V cells per module


Electrical

Input voltage:

90 to 300VDC

Power consumption: 5W
Ground fault detection: 0 to 10mA

Mechanical

 
Mounting: CXCR with 19" or 23" rack mounting
CXCP panel mount

Dimensions
CXCP/R
(Plus 19" or 23" bracket)
mm: 131H x 431W x 100D
in: 5.1H x 16.9W x 3.9D
Weight: 6.2kg (13.8lb)

Environmental
Temperature: -40 to 65°C (-40 to 149°F)
Humidity: 0 to 95% RH non-condensing

Standards
Safety: CSA/UL 60950-1-03
Emissions:


 
CFR47 (FCC) Part 15 Class A
FCC Part 68
ICES-03 Class A
CE mark
EN55022 (CISPR 22) Class A
C-tick (Australia)
Immunity: EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6