Total Power Solutions
Our catalogues

Our catalogues

German    English    French
Pinnacle Plus

Pinnacle Plus

Online double conversion UPS

Pinnacle Plus
Data sheet
Downloads
Source of supply

The Alpha Pinnacle Plus Series provides safe, clean and reliable power protection for computer, telecom and other mission critical equipment. The state of the art DSP (Digital Signal Processing) technology of the Pinnacle Plus Series provides pure sine wave and zero transfer time backup power. Both RS-232 and USB ports are available to provide two-way communication to local workstations, servers and with the optional network SNMP interface card full network communications are available.

Additional features include: Programmable Load Segmentation making it possible to save battery power for the most critical equipment, fax and modem surge protection, high efficiency mode, multiple language LCD display and (DC Power on) cold start. Advanced battery management, system diagnostics and user “hot swap” battery replacement capability ensures continous power availability.

  • True online technology provides total power protection
  • Pure sine wave output with less than 3% THD
  • Advanced Battery Management (ABM)
  • Automatic System Diagnostics
  • Programmable Load Segmentation (PLS)
  • Emergency Power Off function (EPO)
  • Extended Backup Times up to 8 hours at full load

Variants Technical data

Technical Specifications
Standgeräte PIN+700
PIN+1000
PIN+1500
PIN+2000
PIN+3000
PIN+6000
PIN+8000
PIN+10000
19" RM: PIN+700
RM
PIN+1000 RM PIN+1500 RM PIN+2000 RM PIN+3000 RM PIN+6000 RM - -

Input
               
Capacity (VA): 700 1000 1500 2000 3000 6000 8000 10000
Capacity (W): 490 700 1050 1400 2100 420 5600 7000
Volatage (V): 220-240 220-240 220-240 220-240 220-240 220-240 220-240 220-240
Voltage
Range (V):
160-276 160-276 160-276 160-276 160-276 160-276 160-276 160-276
Frequency (Hz): 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Display
Alarm:
Auto Sensing
Ton 5.Sek.
Auto Sensing
Ton 5.Sek.
Auto Sensing
Ton 5.Sek.
Auto Sensing
Ton 5.Sek.
Auto Sensing
Ton 5.Sek.
Auto Sensing
Ton 5.Sek.
Auto Sensing
Ton 5.Sek.
Auto Sensing
Ton 5.Sek.

Battery
               
DC Voltage 24V 36V 36V 72V 72V 240V 240V 240V
Batteries: 2 x 7Ah 3 x 7Ah 3 x 7Ah 3 x 9Ah 6 x 9Ah 20 x 7Ah 20 x 7Ah 40 x 9Ah
Typical Recharge Time: 4Std. 4Std. 4Std. 4Std. 4Std. 4Std. 4Std. 4Std.
Cold Start: Yes Yes Yes Yes Yes Yes Yes Yes
Runtime at 100% Load: 7min 7min 6min 7min 6min 7min 6min 14min

Physical
               
Input Inlet: IEC 320 IEC 320 IEC 320 IEC 320 IEC 320 Hardwire Hardwire Hardwire
Receptacles: IEC 320 IEC 320 IEC 320 IEC 320 IEC 320 Hardwire Hardwire Hardwire
Total Receptacles: 4 4 4 8/5 8/5 Hardwire Hardwire Hardwire
Dimensions:                
Tower (mm)                
B (mm): 152 152 152 225 225 257 257 320
D (mm): 240 240 240 298 298 570 700 863
H (mm): 420 420 420 420 420 585 690 740
19“Rackmount                
B (mm): 428 428 428 428 428 428 - -
D (mm): 84 84 84 84 84 252 - -
H (mm): 420 420 420 635 635 597    
Weight: 13,5 16,2 17,0 31,1 33,0 86 112 190
Tower (kg): 15,5 17,1 18,1 31,6 32,5 86 - -
19“Rackmount                

Environment
               
Audible
noise:
<40dB(A) <40dB(A) <40dB(A) <40dB(A) <40dB(A) <40dB(A) <40dB(A) <40dB(A)
Operating
Temperature:
0 - 40° C 0 - 40° C 0 - 40° C 0 - 40° C 0 - 40° C 0 - 40° C 0 - 40° C 0 - 40° C
Storage
Temperature:
-20-50° C -20-50° C -20-50° C -20-50° C -20-50° C -20-50° C -20-50° C -20-50° C
Altitude: 3500m 3500m 3500m 3500m 3500m 3500m 3500m 3500m
Relative
Humidity:
0 to 95%,
non-condensing
0 to 95%,
non-condensing
0 to 95%,
non-condensing
0 to 95%,
non-condensing
0 to 95%,
non-condensing
0 to 95%,
non-condensing
0 to 95%,
non-condensing
0 to 95%,
non-condensing

Allgemeines
Output
Voltage (V):
Frequency (Hz):
Transfer Time (ms):
High Efficiency Mode:
UPS Technology:
Overload Recovery:
Wave Form:
Harmonic Distortion:
Crest Factor:

208/220/230/240 adjustable
50/60Hz ±0.5
0
>95% im High Efficiency Mode
Online (IEC 62040-3: VFI-SS-111)/Microprocessor controlled
Auto Transfer to UPS
Sine wave
<3% of T.H.D with linear load
3:1
Battery
Type:
Management:
Battery Protection:

Sealed, maintenance free lead acid batteries
Self-test, adjustable battery transfer points and alarm settings
Deep discharge protection
Protection
Surge:
Overload:
Short Circuit:

Meets EN 61000-4-5 level 3
Auto shut down if overlaod exceeds 125% for 1min and 150% for 10sec
UPS output cut off immediately or input fuse/circuit breaker protection
Interface: RS-232 Serial Port and USB (optional SNMP network adaptor card)
System
Audible Alarm
Battery Backup:
Battery Low:
UPS Fault:


Beep every 5sec
Two Beeps every 5sec
Continuous beeping sound and LCD Display
Certification
Safety:
EMC:
Warranty:

EN 50091-1, EN 60950, CE
EN 50091-2, EN 50022/B, FCC Part 15, CISPR 22
24 Months